PVIENG27654458LKD PUMP designed for the realisation of pressurization units in water systems and filling of pressure vessels.
Suitable for sprinkler systems and other general water supply uses.
SPECIFICATION:
Operating range: from 1,2 to 30 m3/h with head up to 97 metres.
Pumped liquid: clean, free of solids and abrasives, non-viscous, non-
aggressive, non-crystallised and chemically neutral, with properties similar
to water.
Liquid temperature range:
K 35/40, K 45/50,
K 35/100, K 40/100, K 55/100 :from -10 °C to +50 °C
K 55/50, K 66/100, K 90/100
K 70/300, K 80/300, K 70/400, K 80/400 :from -15 °C to +110 °C
Maximum ambient temperature: +40°C
Maximum operating pressure:
K 35/40, K 35/100, K 40/100 :6 bar (600 kPa)
K 45/50, K 55/50 :8 bar (800 kPa)
K 55/100, K 66/100 :10 bar (1000 kPa)
K 90/100, K 70/300, K 80/300, K 70/400, K 80/400 :12 bar (1200 kPa)
Protection class:
IP 55, IP 44 per K 35/40, K 45/50, K 55/50, K 35/100, K 40/100
Protection class at the terminal board: IP 55
Insulation class: F
Standard voltage:
single-phase 220-240 V / 50 Hz
three-phase 230-400 V / 50 Hz up to 4 kW included - 400 V ∆ 50 Hz
from 5,5 kW